Home > Products > Hospital & Healthcare > Laminar Airflow Ceiling
Return to list

Laminar Airflow Ceiling

Applications of laminar flow ceiling systems in cleanrooms: hospital clean operating rooms, clean wards, clean animal rooms, etc.

  •Series:KuCe

Introduction

Modular design

The cleanroom ceiling system consists of several modular units, each manufactured and assembled in the factory. Upon arrival at the site, they are simply assembled and secured to the mounting frame. This modular design not only facilitates transportation but also saves installation time and reduces manpower requirements. The overall height of the enclosure can be designed as low as 450mm.

Sealing

The enclosure is fully welded to ensure airtightness. Multiple mechanical seals are used between modules, and each module has its own independent air supply with no cross-contamination. A liquid-tank type high-efficiency filter is included to ensure no side leakage.

Filter installation

The interior of the housing is equipped with semi-fixed rotating pressure blocks around the perimeter, which can quickly and effectively fix the filter and ensure airtightness.


Clean airflow

Cleanroom ceilings deliver fresh air to the cleanroom at a stable airflow velocity (0.25-0.35m/s), ensuring that pollutants generated in the area are quickly and effectively removed, thus guaranteeing the cleanliness of the room.

Cleanroom ceiling structure diagram

Test

To facilitate on-site testing, cleanroom ceilings can be equipped with dust emission ports and sampling test ports to meet the needs of on-site filter leakage testing in cleanrooms. On-site airflow direction and velocity testing can also be provided.

Material

The enclosure is made of 2mm thick cold-rolled steel plate, which is fully welded, giving it high strength. The surface is treated with electrostatic powder coating, and it has good resistance to standard disinfectants and cleaning agents used in hospitals.

Clean operating room classification standards (empty or static state)

Technical Specification for Clean Operating Room Buildings in Hospitals GB 50333-2013

The surgical area of a Class I operating room refers to the area extending at least 0.9m outward from each side of the operating table and at least 0.4m outward from each end of the operating table (including the operating table).

The surgical area of a Class II operating room refers to the area (including the operating table) that extends at least 0.6m outward from each side of the operating table and at least 0.4m outward from each end.

The surgical area of a Class III operating room refers to the area at least 0.4m behind each of the four sides of the operating table (including the operating table).

Technical Specifications

ParameterSS-ⅠSS-ⅡSS-Ⅲ
Filtration Efficiency99.995%@0.3μm99.995%@0.3μm99.995%@0.3μm
Outlet Air Velocity (m/s)0.450.30.23
Overall Dimensions (mm)2600X2400X5102600X1800X5102600X1400X510
Air Supply Area Dimensions(mm)2600X24002600X18002600X1400
Flange Dimensions(mm)800x200-4pcs500x200 -4 pcs500x200 -4 pcs
Filter Dimensions(mm)1170X687X69 - 4 pcs1170X486X69 - 4 pcs1390x390x69 - 2 pcs
965X687X69 - 2 pcs965X486X69 - 2 pcs990X800X69 - 2 pcs
ApplicationClass Ⅰ Operating RoomClass Ⅱ Operating RoomClass Ⅲ Operating Room
Filter TypeMinipleat High Efficiency, Liquid Tank SealMinipleat High Efficiency, Liquid Tank SealMinipleat High Efficiency, Liquid Tank Seal
Clean Ceiling Box MaterialHigh-quality Cold-rolled Steel Plate with Plastic SprayHigh-quality Cold-rolled Steel Plate with Plastic SprayHigh-quality Cold-rolled Steel Plate with Plastic Spray
Outlet Panel MaterialPolymer Uniform Flow MembranePolymer Uniform Flow MembranePolymer Uniform Flow Membrane