Fogging shower
A mist shower is a purification device installed on the wall of a cleanroom for daily operation or emergency use. Its conventional function is to encapsulate and wrap drug powders (mainly APIs) on disposable work clothes. It is mainly used in biological laboratories, pharmaceuticals, and the chemical industry.
•Series:KuFo
Introduction

Fogging shower Room
A mist shower is a purification device installed on the wall of a cleanroom for daily operation or emergency use. Its conventional function is to encapsulate and wrap drug powder (mainly API) on disposable work clothes. For reusable work clothes, after encapsulating and wrapping the drug powder on the surface of the clothing, water mist can be used to rinse and circulate the powder to remove it without affecting the use and appearance of the work clothes.
The mist shower room also has an air blowing function, which provides circulating air during operation to maintain the air cleanliness inside the mist shower room.
Application areas of mist shower rooms
It is mainly used in daily or emergency situations in the pharmaceutical, biological laboratories, and chemical industries to package drug powder on work clothes.
Working principle of mist shower room
The air shower function of the mist shower room keeps the internal air clean. The mist shower device generates a low-velocity wet mist that can encapsulate the APIs (active pharmaceutical ingredients) on the work clothes, continuously forming larger particles. As the particles continue to grow larger, they form droplets and eventually water droplets, which fall off the clothes, thus keeping the workers' clothes clean and dry.
Product Advantages
Visual design, real-time monitoring of work status
The recirculating air design ensures the cleanliness of the mist shower chamber when not in operation.
High-efficiency filters can achieve an efficiency of H14 (EN1822).
Sensor control, automatically starts the air shower cycle
Double-door electromagnetic interlock, automatic door closer
Emergency stop buttons are installed on both sides of the doors and inside the room to deal with emergencies.
Optional static eliminator and safe filter replacement method


Structural design
The enclosure is made of stainless steel with a water collection system, which is rust-proof, dustproof, and easy to clean. The mist spray nozzles and lighting are located at the top, while the air shower nozzles are located on the side walls. Air supply and return ducts are located behind the wall panels to reduce liquid on clothing and provide rapid ventilation within the mist shower chamber. A double-glazed viewing window allows for easy monitoring of the operating status. A perforated design at the bottom channels the water pipes. The mist shower chamber's components feature a quick-change design to minimize downtime in case of equipment malfunctions requiring maintenance.
Human-centered design
The PLC controller is equipped with a visual touch screen that can display the misting process and status. Once any abnormality occurs in the equipment, the internal alarm device will be activated, providing real-time alarm prompts. Alarm information can be viewed and alarm prompts can be cleared on the display screen. Administrators can adjust the misting cycle and change the blowing time, and can set multi-level management permissions to facilitate operation by managers at all levels.
Sensor control, automatic air shower, mist shower and air shower time are adjustable, and timer, cycle and emergency status can all be set by the user.
Work process of mist shower room
When the mist shower room is powered on, the power indicator light illuminates. Manually open the outer door, and the double doors interlock. The interior lights of the mist shower room turn on, and staff enter the mist shower room and close the door. After the internal sensor detects the mist shower, the mist shower cycle begins. After the mist shower cycle ends, the program automatically starts the air shower cycle. After the air shower cycle ends, the interlock is released, staff open the inner door, leave the mist shower room and enter the clean area, close the door, and the cycle ends.

Technical Specifications
| Item | Parameters |
|---|---|
| Material | SSUS 304 |
| Compressed Air | 0.6-0.8 bar |
| Control | Touch screen + PLC |
| Power Supply | AC 220 V/50 Hz |
| Door | Standard waterproof door, airtight door |
| Fogging shower Nozzle | Top spray |
| Fogging shower Duration | Factory setting: 15 s (adjustable) |
| Water Fogging Particle Size | 1—10μm |
| Air Shower Cycle Capacity (persons) | 1 person |
| Personnel Throughput Rate (persons/minute) | 4 persons/minute |
| Fresh Air | Indoor air intake |
| Exhaust Air | Exhaust to outdoors or duct |
| Exhaust Fan | EBM |
| Exhaust HEPA Filter | H14 99.995%@MPPS |
| Drainage | Connected to floor drain |
| Water Replenishment | Connected to water pipe or manual refill |