Home > Products > Hospital & Healthcare > Air Filtration Unit
Return to list

Air Filtration Unit

An air filtration unit, also known as an air filtration unit, is installed at the end of an exhaust system and is also called an exhaust box. It can effectively filter out harmful gases and infectious viruses generated during production or biological operations. It is mainly used in the supply and exhaust sections of clean rooms, hospital operating rooms, biological laboratories, and other similar locations.

  •Series:KuFu

Introduction

Air Filtration Unit ( Air Filter Unit ) – KuCo Series

Air Filtration Units/air filtration units are installed at the end of the exhaust system to effectively filter out harmful gases and infectious viruses generated during production or biological operations. These filter boxes can be installed before or after the fresh air handling unit to ensure full utilization of existing air conditioning equipment resources while carrying out purification upgrades and reducing project costs .

The advantages of air filtration units: Installed before or after fresh air handling units, they can fully utilize existing air conditioning equipment resources. They can provide various gas purification and filtration treatments for centralized supply and exhaust air sections. Multiple filtration methods: fiber filtration, physical adsorption, chemical decomposition, etc. Diverse filtration functional sections: water and oil removal section, pre-filter section , medium-efficiency filter section, high-efficiency filter section, activated carbon adsorption section, chemical action section, etc.


Air Filtration Unit provides multiple filtration

The water and oil removal sections are used to filter water and oil from the air. The primary and medium-efficiency filtration sections are mainly used to filter dust particles larger than 1µm, with filtration efficiency levels ranging from G3 to F9 (EN779). The high-efficiency filtration section is used to filter tiny suspended particles smaller than 1µm, with filtration efficiencies reaching U16 (EN1822). After filtration through this section, the outlet gas can achieve a cleanliness level of over Class 100. The activated carbon adsorption section is used to filter large molecular harmful gases, such as formaldehyde and VOCs. Activated carbon can effectively filter out these components in mixed gases, with a filtration efficiency of up to 98%. The chemical action section is used to filter out acidic or alkaline gases, such as chlorine and ammonia . Filtration sections impregnated with different chemical solutions can filter out these gases, with a filtration efficiency of up to 95%.

Air Filtration Units offer a variety of sealing methods

In addition to the mechanical seal of the gasket, the filter box/air filtration unit also provides a liquid tank seal. The liquid tank seal can completely eliminate gas leakage between the filter and the frame, and when used with an ultra-high efficiency filter, it can achieve an air outlet cleanliness level of over 10.

Primary filter fiber, high-efficiency filter fiber, activated carbon granules, chemical granules
Stacked installation, V-shaped installation, bag-in-bag-out installation

Air filter installation method is optional

To reduce the length of the housing, stacked installation can be adopted; to increase the filtration area and reduce the pressure loss of the filtration section, V-type installation can be adopted; to protect the safety of maintenance personnel and prevent harmful substances such as viruses captured by the filter from injuring the personnel replacing the filter, bag-in-bag-out installation and replacement can be adopted .

Technical Specifications

ModelKuFu02NOSNKuFu02D1SFKuFuOIDISF
Dimensions (H*W*L)900*1280*1600mm1010*1310*3200mm620*680*2400mm
Cabinet MaterialSUS 304/316Cold-rolled Steel (Electrostatic Powder Coating)Cold-rolled Steel (Electrostatic Powder Coating)
Airflow Capacity4000 CMH4000CMH2000CMH
External Static Pressure400 Pa400 Pa350 Pa
Filter EfficiencyG4F7G4
Activated Carbon (VOC 95%)Activated Carbon (VOC 95%)F8
Chemical Filtration (NHs 98%)H14 (EN1822)H14 (EN1822)
F7
Power Supply—AC 380 V/50HzAC 380 V/50Hz
Power Consumption—5.5kW3kW
Differential Pressure GaugeDWYER Digital/Pointer TypeDWYER Digital/Pointer TypeDWYER Digital/Pointer Type
Inlet Flange Size600*800mm600*800mm400*600 mm
Outlet Flange Size600*800mm600*800mm400*600 mm

Note: Dimensions and other features can be customized.